The Hall current sensor is mainly suitable for the isolation and conversion of complex signals such as AC, DC, and pulse. It is suitable for current signal acquisition and feedback control of current monitoring and battery applications, inverter power supply and solar power management systems, DC panels and DC motor drives, electroplating, welding applications, inverters, UPS servo control and other systems.
Display

MAIN PARAMETERS
Parameter |
Description&Value |
Rated Input |
0~±(50-500)A DC or 0~(50~500)A AC |
Rated Output |
±5Vdc/±4Vdc |
Accuracy |
Class 1.0 |
Power Supply |
±15Vdc (allow ±20% fluctuation%) |
Consumption |
≤0.5W |
Zero Offset Voltage |
±20mV |
Offset Voltage Drift |
≤±1.0mV/℃ |
Linearity |
≤0.2%FS |
Response Time |
≤5us |
Bandwidth |
0~20kHz |
Isolation Voltage |
3.5kV/50Hz/1min |