AM3SE Series Medium Voltage Protection Relay
OVERVIEW
The AM3SE series of medium voltage protection relay integrate protection and control. They are suitable for user terminal substations (stations) with voltage levels of 35kV and below, can realize the protection and control of user substations. The application areas cover power, water conservancy, transportation, petroleum, chemical industry, coal, metallurgy and other industries.
The protection relay adopts advanced, mature and reliable protection principles and algorithms, with strong anti-interference performance, high reliability, flexible protection implementation methods, and redundant communication design. Also can cooperate with the power monitoring system to provide guarantee for the reliable operation of the user substation distribution automation system.
MAIN PARAMETERS
Power supply |
Rated input |
AC/DC220V, or AC/DC110V, or DC48V, or DC24V |
Range |
Rared Voltage×(1±20%) |
|
Consumption |
≤10W ( DC ) |
|
Rated Voltage |
Rated input |
AC 100V/100/V |
Range |
1~120V |
|
Accuracy |
±0.5% |
|
Consumption |
≤0.5VA (single phase) |
|
Rated Current |
Rated input |
AC 5A /1A |
Range |
0.04In~15In |
|
Accuracy |
±0.5% |
|
Consumption |
≤0.5VA (single phase) |
|
Frequence |
Rated frequency |
50Hz or 60Hz |
Range |
45~55Hz or 60Hz |
|
Accuracy |
±0.1Hz |
|
DI |
Rated Voltage |
AC/DC220V, or AC/DC110V, or DC48V, or DC24V |
Range |
Rared Voltage×(1±20%) |
|
Cconsumption |
≤1W(DC220V)(single channel) |
|
DO |
Mechanical life |
≥10000 |
Switching capacity |
≥1000W,L/R = 40ms |
|
On current |
continuous ≥5A, short time(200ms)≥30A |
|
Interrupting capacity |
≥30W,L/R = 40ms |
|
Environment |
Temperature |
-10℃~+55℃ |
Humidity |
5%~95% (No condensation and freeze inside) |
|
Altitude |
≤4000m |
FUNCTIONS
Main function
[50/51] Overcurrent , 3stages;
[50N/51N]Zero-sequence overcurrent protection (3 stages earth fault);
[59] Over voltage protection;
[27] Under voltage protection;
[81U] Under frequency;
[26/63] Non-electricity protection;
[79] Auto-reclose;
Electrical parameter measurement :U,I,f,P,Q,PF,Ep,Eq,Es
Protection functions |
AM3SE- |
||
I |
U |
||
Overcurrent (3 stages,IDMT) |
■ |
|
|
Earth fault (3 stages,IDMT)(I01/I02) |
■ |
|
|
Negative sequence overcurrent (2 stages,IDMT) |
■ |
|
|
Auto-reclose |
■ |
|
|
Overload (trip/alarm) |
■ |
|
|
Under frequency |
■ |
|
|
Post-accelerated overcurrent |
■ |
|
|
Post-accelerated overcurrent(I01/I02) |
■ |
|
|
Overvoltage(trip) |
■ |
|
|
Undervoltage (trip) |
■ |
|
|
Self-produced over zero-voltage (trip) |
■ |
|
|
Residual overvoltage (trip) |
■ |
|
|
FC block |
■ |
|
|
Trip and close circuit supervision (alarm) |
■ |
|
|
Non-electricity (trip/alarm) |
■ |
|
|
Undervoltage (alarm) |
■ |
■ |
|
Overvoltage (alarm) |
■ |
■ |
|
Residual overvoltage (alarm) |
■ |
■ |
|
PT supervision (alarm) |
■ |
■ |
|
Self-produced over zero-voltage (alarm) |
|
■ |
|
Rear ports |
I |
U |
|
RS485 |
■ |
||
Protocols |
I |
U |
|
Modbus serial |
■ |
||
IEC 60870-5-103 |
■ |
||
Measurement |
I |
U |
|
Electric parameter |
U,I,P,Q,PF,Fr,Ep,Eq,Es |
||
Input Current |
5 |
0 |
|
Input Voltage |
3 |
3 |
|
Logs and Records |
I |
U |
|
Fault recorder |
■ |
||
Sequence of event record |
■ |
||
Monitoring Functions |
I |
U |
|
Anti-pumping circuit |
Optional |
|
|
Remote control |
■ |
||
Protection functions |
AM2SE- |
||
V |
H |
||
Overcurrent (3 stages,IDMT) |
■ |
||
Earth fault (3 stages,IDMT) |
■ |
||
Negative sequence overcurrent (2 stages,IDMT) |
■ |
||
Auto-reclose |
■ |
||
Overload (trip/alarm) |
■ |
||
Under frequency |
■ |
||
Post-accelerated overcurrent |
■ |
||
I0 Post-accelerated overcurrent |
■ |
||
Overvoltage(trip) |
■ |
||
Undervoltage (trip) |
■ |
||
Self-produced over zero-voltage (trip) |
■ |
||
Residual overvoltage (trip) |
■ |
||
FC block |
■ |
||
Trip and close circuit supervision (alarm) |
■ |
||
Non-electricity (trip/alarm) |
■ |
||
Undervoltage (alarm) |
■ |
||
Overvoltage (alarm) |
■ |
||
Residual overvoltage (alarm) |
■ |
||
PT supervision (alarm) |
■ |
||
Self-produced over zero-voltage (alarm) |
■ |
||
Rear ports |
V |
H |
|
RS485 |
■ |
||
Protocols |
V |
H |
|
Modbus serial |
■ |
||
IEC 60870-5-103 |
■ |
||
Measurement |
V |
H |
|
Electric parameter |
U,I,P,Q,PF,Fr,Ep,Eq,Es |
||
Input Current |
4 |
||
Input Voltage |
3 |
||
Logs and Records |
V |
H |
|
Fault recorder |
■ |
||
Sequence of event record |
■ |
||
Monitoring Functions |
V |
H |
|
Anti-pumping circuit |
Optional |
||
Remote control |
■ |
DIMENSION
PACKAGE
⚫ HS Code: 8536300000
⚫ Net Weight: 1.02kg/pcs
⚫ Package: 300×220×150cm/pcs