AM3SE Series Medium Voltage Protection Relay

● A complete set of protection, related to the application;
● 3 current input, 3 voltage input, 11DI, 5DO;
● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V, DC48V, DC24V;
● 1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU;
● 1 GPS for GPS timing;
● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records;
● Powerful graphic programmable Logic.

    OVERVIEW

    The AM3SE series of medium voltage protection relay integrate protection and control. They are suitable for user terminal substations (stations) with voltage levels of 35kV and below, can realize the protection and control of user substations. The application areas cover power, water conservancy, transportation, petroleum, chemical industry, coal, metallurgy and other industries.
    The protection relay adopts advanced, mature and reliable protection principles and algorithms, with strong anti-interference performance, high reliability, flexible protection implementation methods, and redundant communication design. Also can cooperate with the power monitoring system to provide guarantee for the reliable operation of the user substation distribution automation system.

    MAIN PARAMETERS

    Power supply

    Rated input

    AC/DC220V, or AC/DC110V, or DC48V, or DC24V

    Range

    Rared Voltage×(1±20%)

    Consumption

    ≤10W ( DC )

    Rated Voltage

    Rated input

    AC 100V/100/V

    Range

    1~120V

    Accuracy

    ±0.5%

    Consumption

    ≤0.5VA  (single phase)

    Rated Current

    Rated input

    AC 5A /1A

    Range

    0.04In~15In

    Accuracy

    ±0.5%

    Consumption

    ≤0.5VA  (single phase)

    Frequence

    Rated frequency

    50Hz or 60Hz

    Range

    45~55Hz or 60Hz

    Accuracy

    ±0.1Hz

    DI

     Rated Voltage

    AC/DC220V, or AC/DC110V, or DC48V, or DC24V

    Range

    Rared Voltage×(1±20%)

    Cconsumption

    ≤1W(DC220V)(single channel)

    DO

     Mechanical life

    ≥10000

    Switching capacity

    ≥1000W,L/R = 40ms

    On current

     continuous ≥5A, short time(200ms)≥30A

     Interrupting capacity

    ≥30W,L/R = 40ms

    Environment

    Temperature

    -10℃~+55℃

    Humidity

    5%~95% (No condensation and freeze inside)

    Altitude

    ≤4000m

    FUNCTIONS

    Main function

    [50/51] Overcurrent , 3stages;

    [50N/51N]Zero-sequence overcurrent protection (3 stages earth fault);

    [59] Over voltage protection;

    [27] Under voltage protection;

    [81U] Under frequency;

    [26/63] Non-electricity protection;

    [79] Auto-reclose;

    Electrical parameter measurement :U,I,f,P,Q,PF,Ep,Eq,Es

     

    Protection functions

    AM3SE-

    I

    U

    Overcurrent (3 stages,IDMT)

     

    Earth fault (3 stages,IDMT)(I01/I02)

     

    Negative sequence overcurrent (2 stages,IDMT)

     

    Auto-reclose

     

    Overload (trip/alarm)

     

    Under frequency

     

    Post-accelerated overcurrent

     

    Post-accelerated overcurrent(I01/I02)

     

    Overvoltage(trip)

     

    Undervoltage (trip)

     

    Self-produced over zero-voltage (trip)

     

    Residual overvoltage (trip)

     

    FC block

     

    Trip and close circuit supervision (alarm)

     

    Non-electricity (trip/alarm)

     

    Undervoltage (alarm)

    Overvoltage (alarm)

    Residual overvoltage (alarm)

    PT supervision (alarm)

    Self-produced over zero-voltage (alarm)

     

    Rear ports

    I

    U

    RS485

    Protocols

    I

    U

    Modbus serial

    IEC 60870-5-103

    Measurement

    I

    U

    Electric parameter

    U,I,P,Q,PF,Fr,Ep,Eq,Es

    Input Current

    5

    0

    Input Voltage

    3

    3

    Logs and Records

    I

    U

    Fault recorder

    Sequence of event record

    Monitoring Functions

    I

    U

    Anti-pumping circuit

    Optional

     

    Remote control

    Protection functions

    AM2SE-

    V

    H

    Overcurrent (3 stages,IDMT)

    Earth fault (3 stages,IDMT)

    Negative sequence overcurrent (2 stages,IDMT)

    Auto-reclose

    Overload (trip/alarm)

    Under frequency

    Post-accelerated overcurrent

    I0 Post-accelerated overcurrent

    Overvoltage(trip)

    Undervoltage (trip)

    Self-produced over zero-voltage (trip)

    Residual overvoltage (trip)

    FC block

    Trip and close circuit supervision (alarm)

    Non-electricity (trip/alarm)

    Undervoltage (alarm)

    Overvoltage (alarm)

    Residual overvoltage (alarm)

    PT supervision (alarm)

    Self-produced over zero-voltage (alarm)

    Rear ports

    V

    H

    RS485

    Protocols

    V

    H

    Modbus serial

    IEC 60870-5-103

    Measurement

    V

    H

    Electric parameter

    U,I,P,Q,PF,Fr,Ep,Eq,Es

    Input Current

    4

    Input Voltage

    3

    Logs and Records

    V

    H

    Fault recorder

    Sequence of event record

    Monitoring Functions

    V

    H

    Anti-pumping circuit

    Optional

    Remote control

    DIMENSION

    DIMENSIONkz9

    PACKAGE

    ⚫ HS Code: 8536300000

    ⚫ Net Weight: 1.02kg/pcs

    ⚫ Package: 300×220×150cm/pcs

     

    APPLICAITON

    ⚫ Municipal Construction
    ⚫ Hospitals
    ⚫ Schools
    ⚫ Hotels
    ⚫ Commercial Buildings
    wiringr4gwiring-1x4p

    INSTALLATION CONSTRUCTION

    Installation-1a8y

    Main view

    Installation-2591

    side view

    Installation-3y9e

    hole view

    WIRING

    wiringr4g wiring-1x4p wiring-2ic8

    Download_file
    [Certificate 2023.06.21] CE Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] CE-RED Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] IEC Certificate ADW300 Series
    Download_file
    [Certificate 2023.06.21] LVD Certificate of ADW300 Series
    Download_file
    [Datasheet 2023.06.21] ADW300 3-phase Wireless Energy Meter
    Download_file
    [Instruction 2023.08.31] ADW300 Common FAQ & Trouble Shooting
    Download_file
    [Instruction 2023.08.31] ADW300 Keypad Configuration Manual