AM5SE Series Medium Voltage Protection Relay
OVERVIEW
The AM5SE series Medium Voltage relay integrates protection, control, measurement, communication and monitoring functions. It is rich in resources, well-configured, easy to maintain and has stable performance. It is suitable for the protection and control of power systems with voltage levels of 35kV and below, and realizes the protection of incoming lines, main transformers, distribution transformers, motors, capacitors, busbars, PTs, etc. The application areas cover power, water conservancy, transportation, petroleum, chemical industry, coal, metallurgy and other industries.
The device hardware design adopts reliability configuration, and the software is equipped with a special protection algorithm. It has strong anti-interference performance, high reliability, and flexible protection implementation methods. It can be used in conjunction with power monitoring system to provide protection for the safe and reliable operation of the power system.
MAIN PARAMETERS
Power supply |
Rated input |
AC/DC220V, or AC/DC110V |
Range |
Rared Voltage×(1±20%) |
|
Consumption |
≤15VA |
|
Rated Voltage |
Rated input |
AC 100V/100/V |
Range |
0.1~120V |
|
Accuracy |
±0.5% |
|
Consumption |
≤0.5VA (single phase) |
|
Rated Current |
Rated input |
AC 5A /1A |
Range |
0.04In~1.2In |
|
Accuracy |
±0.5% |
|
Consumption |
≤0.5VA (single phase) |
|
Frequence |
Rated frequency |
50Hz or 60Hz |
Range |
40~70Hz |
|
Accuracy |
±0.1Hz |
|
DI |
Rated Voltage |
AC/DC220V, or AC/DC110V |
Range |
Rared Voltage×(1±20%) |
|
Cconsumption |
≤1W(DC220V)(single channel) |
|
DO |
Mechanical life |
≥10000 |
Switching capacity |
≥1000W,L/R = 40ms |
|
On current |
continuous ≥5A, short time(200ms)≥30A |
|
Interrupting capacity |
≥30W,L/R = 40ms |
|
Environment |
Temperature |
-10℃~+55℃ |
Humidity |
5%~95% (No condensation and freeze inside) |
|
Altitude |
≤2500m |
|
Protection Level |
IP20 |
FUNCTIONS
Main function
Model Selection
AM5SE-IS-Backup Automatic Switch Protection Relay
AM5SE-D2-Main Transformer Differential
AM5SE-D2-Main Transformer Differential
DIMENSION
PACKAGE
APPLICAITON
INSTALLATION CONSTRUCTION
2.Then put the device into the hole as shown in Figure 2