English
Leave Your Message
AM5SE Series Medium Voltage Protection Relay

Medium Voltage Protection Relay

Products Categories
Featured Products

AM5SE Series Medium Voltage Protection Relay

● A complete set of protection, related to the application;
● 8 current input, 4 voltage input, 16 DI, 10 DO;
● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V;
● 2 RS485 serial communication, IEC 60870-5-101, IEC60870-5-103 and Modbus-RTU;
● 1 RS232 for user update;
● 1 GPS for GPS timing;
● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records;
● Powerful graphic programmable Logic.
● Line protection Motor protection Capacitor protection Feeder protection

    OVERVIEW

    The AM5SE series Medium Voltage relay integrates protection, control, measurement, communication and monitoring functions. It is rich in resources, well-configured, easy to maintain and has stable performance. It is suitable for the protection and control of power systems with voltage levels of 35kV and below, and realizes the protection of incoming lines, main transformers, distribution transformers, motors, capacitors, busbars, PTs, etc. The application areas cover power, water conservancy, transportation, petroleum, chemical industry, coal, metallurgy and other industries.
    The device hardware design adopts reliability configuration, and the software is equipped with a special protection algorithm. It has strong anti-interference performance, high reliability, and flexible protection implementation methods. It can be used in conjunction with power monitoring system to provide protection for the safe and reliable operation of the power system.

    MAIN PARAMETERS

    Power supply

    Rated input

    AC/DC220V, or AC/DC110V

    Range

    Rared Voltage×(1±20%)

    Consumption

    ≤15VA 

    Rated Voltage

    Rated input

    AC 100V/100/V

    Range

    0.1~120V

    Accuracy

    ±0.5%

    Consumption

    ≤0.5VA  (single phase)

    Rated Current

    Rated input

    AC 5A /1A

    Range

    0.04In~1.2In

    Accuracy

    ±0.5%

    Consumption

    ≤0.5VA  (single phase)

    Frequence

    Rated frequency

    50Hz or 60Hz

    Range

    40~70Hz

    Accuracy

    ±0.1Hz

    DI

     Rated Voltage

    AC/DC220V, or AC/DC110V

    Range

    Rared Voltage×(1±20%)

    Cconsumption

    ≤1W(DC220V)(single channel)

    DO

     Mechanical life

    ≥10000

    Switching capacity

    ≥1000W,L/R = 40ms

    On current

     continuous ≥5A, short time(200ms)≥30A

     Interrupting capacity

    ≥30W,L/R = 40ms

    Environment

    Temperature

    -10℃~+55℃

    Humidity

    5%~95% (No condensation and freeze inside)

    Altitude

    ≤2500m

    Protection Level

    IP20

    FUNCTIONS

    Main function

    [67] Overcurrent , 3stages (with direction and voltage lockout);
     [50N/51N] Zero-sequence overcurrent protection (2 stages earth fault);
     [59] Over voltage protection;
     [27] Under voltage protection;
     [26/63] Non-electricity protection;
     [25] Check synchronization;
     [32R] Directional power protection;
     [ATS] Bus tie protection;
     [87T] Transformer differential protection of main transformer;
     Main transformer backup protection;
     Motor protection;
    functionii6

    Model Selection

    AM5SE-IS-Backup Automatic Switch Protection Relay

    main function-7jl5

    AM5SE-D2-Main Transformer Differential

    main function-1dro

    AM5SE-D2-Main Transformer Differential

    main function-27wc

    DIMENSION

    dimension-1064

    PACKAGE

    ⚫ HS Code: 8536300000
    ⚫ Net Weight: 3kg/pcs

    APPLICAITON

    ⚫ 35kV Substation
    ⚫ Industrial and Mining Enterprises
    ⚫ Power Plants
    ⚫ Renewable Power Generation

    INSTALLATION CONSTRUCTION

    The device is installed in a panel embedded manner. 
    1.Make a hole on the screen panel according to the hole size, as shown in Figure 1.
    2.Then put the device into the hole as shown in Figure 2 
    3.Until the device panel is against the cabinet panel. Place the bracket inside the cabinet panel (one bracket on the top and one on the bottom), as shown in Figure 3, 4.Rotate the four fixing screws to firmly fix the device on the cabinet panel, and finally cover the four flaps. (There is a small notch on the top of the flap. When disassembling, you need to insert a flat-blade screwdriver into the small notch to remove the flap.)
    installationr8i13nt
    Download_file
    [Certificate 2023.06.21] CE Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] CE-RED Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] IEC Certificate ADW300 Series
    Download_file
    [Certificate 2023.06.21] LVD Certificate of ADW300 Series
    Download_file
    [Datasheet 2023.06.21] ADW300 3-phase Wireless Energy Meter
    Download_file
    [Instruction 2023.08.31] ADW300 Common FAQ & Trouble Shooting
    Download_file
    [Instruction 2023.08.31] ADW300 Keypad Configuration Manual