Leave Your Message
AMC100-FT Temperature Monitoring Device

Precision Power Distribution Monitoring

Products Categories
Featured Products

AMC100-FT Temperature Monitoring Device

● A+B dual total 30/48 channels NTC temperature monitoring

● 1 channel RS485 communication

    OVERVIEW

    AMC100-FT Series Temperature Monitoring Device have 30/48 channels outlets NTC temperature measurement can monitor the data center distribution cabinet circuit temperature monitoring.
    Acrel AMC100 series AC precision power distribution monitoring device is a measuring device designed specifically for power management of data center servers. The device is compact and can monitor the full electrical parameters, input and output switches and the status of the lightning arrester of A+B two incoming lines and 192 outgoing lines in real time. The alarm thresholds of all measurement channels can be set individually.For the outgoing line ,the limited event triggers the system's sound and light alarms immediately.The whole solution realized the high integration of the monitoring circuits in the volume of the traditional instrument.

    MAIN PARAMETERS

    Instrument model

    AMC100-FT30

    AMC100-FT48

    Number of measuring channels

    30 channels

    48 channels

    Auxiliary power

    Powered by AMC100-ZA,DC 12-24V power supply when used alone

    Function

    Temperature
    Range

    -20℃~150℃

    Communication

    RS485/Modbus-RTU

    Installation Method

    DIN35mm rail or bottom plate installation

    Protection level

    IP20

    Pollution level

    2

    Environment

    Temperature/humidit
    y/elevation

    Working temperature:-20℃~60℃
    Storage temperature:-25℃~70℃
    Relative humidity:≤93%
    Altitude:≤2500m

    Security

    Insulation

    The insulation resistance between all terminals and the conductive parts of the shell is not
    less than 100MQ

    Withstand
    voltage

    AC2kV 1min between auxiliary power supply and temperature measurement,leakage
    current should be less than 2mA,no breakdown or flashover phenomenon

    Electromagnetic
    compatibility

    Anti-static
    interference

    Level 4

    Resistance to
    radio frequency
    electromagnetic
    field radiation

    Level 3

    DIMENSION

    dimension-1

    AMC100-FT48 Dimension

    图片39

    AMC100-FT48 Dimension

    APPLICATION SCENARIOS

    APPLICATION SCENARIOapplication

    WIRING DIAGRAM

    wiring-FT30-1wiring-FT30-2

    AMC100-FT30 Wiring Diagram

    wiring-FT48-1wiring-FT48-2wiring-FT48-3

    AMC100-FT48 Wiring Diagram

    PHOTOS ON SITE

    photo on site-1

    ①AMC100-FAK30/48 Measure 30/48 channels of each circuit of A+B outgoing line
    ②AMC100-ZA  Measure A+B independent 2 circuits three-phase main incoming line
    ③RS485 communication line
    ④AKH-0.66W Type ct or AKH-0.66-EMS type (50,100,200400A)/50mA
    ⑤AKH-0.66/30I Tpye ct
    ⑥ATP007kt 7-inch Touch screen or ATP010kt 10-inch Touch screen

    photos on site-1photos on site-2

    INSTALLATION INSTRUCTION

    INSTALLATION

    Type

    Panel size (mm)

    Shell size (mm)

    Hole size (mm)

    ASJ10

     

    85*54*64 (length*width*height)

     

    ASJ20

    48*48(Width*Height)

    43.8*43.8*100(width*height*depth)

    45*45(Width*Height)

    Download_file
    [Certificate 2023.06.21] CE Certificate of ADW300 Series