AMC100-ZD DC Incoming Line Monitoring Device
OVERVIEW
AMC100-ZD DC Incoming Line Monitoring Device can monitor the voltage, current, power, and electric energy of 2 independent incoming lines A+B,8 switching input, 4 swiching output,one channel temperature and humidity detection,and 3 channels RS485 communications.
Acrel AMC100 series AC precision power distribution monitoring device is a measuring device designed specifically for power management of data center servers. The device is compact and can monitor the full electrical parameters, input and output switches and the status of the lightning arrester of A+B two incoming lines and 192 outgoing lines in real time. The alarm thresholds of all measurement channels can be set individually.For the outgoing line ,the limited event triggers the system's sound and light alarms immediately.The whole solution realized the high integration of the monitoring circuits in the volume of the traditional instrument.
MAIN PARAMETERS
Instrument model |
AMC100-ZD |
|
Measurement Parameters |
Voltage,Current, Power, Electric energy, Ambient temperature and Humidity
|
|
Bus voltage |
Rated |
48VDC,240VDC,336VDC |
Measuring range |
±20% |
|
Overload |
Instantaneous voltage 2 times/sec |
|
Current incoming circuit |
Rated |
5V(Hallsensor, ±12V powered by AMC100-ZD) |
Range |
0~6A |
|
Overload |
Continuous 1.2 times, instantaneous 10 times/sec |
|
Temperature and humidity |
Temperature Range |
-40℃~+99℃ |
Humidity Range |
20%~90% |
|
Measurement accuracy |
Incoming line |
Voltage/current level 0.5, power/electric energy level 1 |
Temperature |
±1℃ |
|
Humidity |
±5% |
|
Auxiliary power |
AMC100-ZD:Signal power(≤15W) AMC100-ZD-P24:DC 12-24V independent powersupply AMC100-ZD-P220: 1.When the constant voltage is DC240V、DC336V,powered by AC220V、 DC240V、DC336V independentsupply 2.When the constant voltage is DC48V,powered by DC48V independentsupply |
|
Environment |
Temperature |
Operation:-15℃~55℃ Storage:-25℃~70℃ |
Humidity |
Relative humidity≤93% |
|
elevation |
≤2500m |
|
Switch output |
4 channels 3A 250VAC/3A 30VDC |
|
Switch input |
8 dry nodes |
|
Communication |
1 isolated RS485/Modbus-RTU to the background system 1 RS485/Modbus-RTU to touch screen |
|
Installation Method |
DIN35mm rail or bottom plate installation |
|
Protection level |
IP20 |
|
Pollution level |
2 |
|
Security |
Insulation |
The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ |
Withstand voltage |
Voltage and current signal of line A // Voltage and current signal of lineB // Switching output //Isolated communication port // Two of other ports should meet AC 2kV for 1 min,switching input and other ports should meet AC0.5kV for 1 min, leakage current should be less than 2mA, no breakdown or flashover phenomenon.
|
|
Electromagnetic compatibility |
Anti-static interference |
Level 4 |
Anti-electric fast transient burst |
Level 3 |
|
Anti-surge interference |
Level 4 |
|
Resistance to radio frequency electromagnetic field |
Level 3 |
DIMENSION

MATCHED CURRENT TRANSFORMER
![]() AKH-0.66-EMS |
![]() |
![]() AKH-0.66-9N-HB AKH-0.66-12N-HB AKH-0.66-20-HB AKH-0.66-30N-HB |
![]() |
APPLICATION SCENARIOS

WIRING DIAGRAM

INSTALLATION INSTRUCTION

PHOTOS ON SITE

①AMC100-FAK30/48 Measure 30/48 channels of each circuit of A+B outgoing line
②AMC100-ZA Measure A+B independent 2 circuits three-phase main incoming line
③RS485 communication line
④AKH-0.66W Type ct or AKH-0.66-EMS type (50,100,200400A)/50mA
⑤AKH-0.66/30I Tpye ct
⑥ATP007kt 7-inch Touch screen or ATP010kt 10-inch Touch screen