AMC200(L)-12DE DC Multi-Circuits Energy Meter(12 circuits)
OVERVIEW
AMC200(L) DC multi-circuit energy meter is mainly used for the full electrical parameter measurement of multiple circuits, and can be connected to the current input of up to 12 single-phase DC circuits at the same time. It can directly measure parameters such as voltage, current and power.
MAIN PARAMETERS
|
Technical Parameter |
Technical Indicator |
||
|
Input |
DC Voltage |
One channel:DC -48V |
|
|
DC Current |
12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access |
||
|
State Grid Monitoring |
One channel:DC 0-5V |
||
|
Overload |
Voltage: 1.2 times for 1 second, 2 times for 1 second; Current: 1.2 times for 1 second, 10 times for 1 second |
||
|
Frequency |
|||
|
Resolution |
The voltage output accuracy is 0.01V, the current output accuracy is 0.01A, the power output accuracy is 0.01kW, and the power output accuracy is 0.01kWh |
||
|
Function |
Basic Function |
Monitoring equipment system time, total voltage, total output current, total power, total electrical energy, voltage of each sub channel, current of each sub channel, power of each sub channel, electrical energy of each sub channel; RS485 communication |
|
|
Alarm Function |
DC voltage output too low alarm, DC voltage output too high alarm, one-time power-off alarm, module voltage loss alarm, metering sub channel error alarm, internal program error alarm, clock error alarm, memory unit failure alarm, AC input power failure alarm |
||
|
Timing function |
Support broadcast timing, remote timing calibration of metering module can be carried out through RS485 communication interface |
||
|
Communication |
|||
|
Hall power supply |
A set of ±12V power output |
||
|
Humidity And Temperature |
4 Channels NTC Temperature Monitoring:Temperature:-20-100℃(Accuracy±2℃) Humidity:20-90%RH(Accuracy ±5%RH) |
||
|
Auxiliary power |
Voltage Range |
DC -40V~-60V |
|
|
Power consumption |
The whole device≤2W (without Hall power supply output) |
||
|
Storage |
It has the storage function of historical energy data and historical alarm information |
||
|
Insulation resistance |
≥40MΩ |
||
|
Environment |
Temperature |
Working Temperature:-20℃~+60℃;Storage Temperature:-40℃~+70℃ |
|
|
Humidity |
≤98% no condensation, no corrosive gas place |
||
|
Altitude |
≤4000m |
||
DIMENSION
Recommend Hall Current Sensor
|
Model |
Specification |
|
AHKC-EKA |
50A/5V Diameter Φ40mm |
|
AHKC-EKB |
100A/5V Diameter Φ40mm |
|
AHKC-K |
200A/5V Diameter Φ64*16mm |
Wiring Terminals and Connections
AMC200L-12DE
|
Terminal Number |
Definition |
Instruction |
Remark |
|
1 |
V+ |
Auxiliary power |
DC 40-60V |
|
2 |
V- |
||
|
11 |
U+ |
Voltage input |
DC 48V |
|
14 |
U- |
||
|
21 |
A |
Communication |
RS485 Communication |
|
22 |
B |
||
|
30 |
DI1 |
Switch input |
Passive dry contact input |
|
31 |
DI2 |
||
|
32 |
DI3 |
||
|
33 |
DI4 |
||
|
39 |
COM2 |
||
|
34 |
DI5+ |
Active switch input |
AC 220V state grid or generator signal access |
|
35 |
DI5- |
||
|
36 |
DI6+ |
||
|
37 |
DI6- |
||
|
40 |
D01 |
relay output |
AC 250V/3A DC 30V/3A; Normally open contact output; contact capacity: AC 250V/3A DC 30V/3A; |
|
42 |
DO2 |
||
|
49 |
COM1 |
||
|
51 |
+12V |
Hall Current sensor power supply |
Provide power to 12 hall current sensor at the same time |
|
52 |
12G |
||
|
53 |
-12V |
||
|
61 |
AI+ |
State Grid Monitoring |
DC 0-5V |
|
62 |
AI- |
||
|
91 |
T1 |
NTC Temperature Monitoring |
Temperature Range:-20-100℃(Accuracy ±2℃) |
|
92 |
T2 |
||
|
93 |
T3 |
||
|
95 |
T4 |
||
|
94 |
COM3 |
||
|
97 |
VSS |
Humidity And Temperature Monitoring |
|
|
98 |
Data |
||
|
99 |
Clk |
||
|
100 |
VDD |
||
|
|
CH1-CH4 |
Number of current Circuit |
One CHx represents 3 single-phase DC circuits, AMC200L-12DE can connect up to 12 single-phase circuits; |
Voltage, current and Hall current sensor wiring method (the figure below takes one channel as an example)

AMC200L Voltage Current And Hall Current Sensor Wiring Method
Note: A group of two Hall connecting lines needs to be connected to the M terminals. For example: the yellow lead wire of one connecting line is a group of yellow and black, corresponding to the yellow part of the above picture, and needs to be connected to the same group of yellow lines and black lines.
Humidity And Temperature Sensor Wiring Method
INSTALLATION INSTRUCTION

Din Rail Installation