AMC200(L)-12DE DC Multi-Circuits Energy Meter(12 circuits)
Multi Circuit Energy Meter
Products Categories
Featured Products

AMC200(L)-12DE DC Multi-Circuits Energy Meter(12 circuits)

● 12 single-phase DC circuits;

● Monitoring equipment system time, total voltage, total output current, total power, total electrical energy, voltage of each sub channel, current of each sub channel, power of each sub channel, electrical energy of each sub channel; RS485 communication

● Alarm Function:DC voltage output too low alarm, DC voltage output too high alarm, one-time power-off alarm, module voltage loss alarm, metering sub channel error alarm, internal program error alarm, clock error alarm, memory unit failure alarm, AC input power failure alarm

● Time Function:Support broadcast timing, remote timing calibration of metering module can be carried out through RS485 communication interface

    OVERVIEW

    AMC200(L) DC multi-circuit energy meter is mainly used for the full electrical parameter measurement of multiple circuits, and can be connected to the current input of up to 12 single-phase DC circuits at the same time. It can directly measure parameters such as voltage, current and power.

    MAIN PARAMETERS

    Technical Parameter

    Technical Indicator

    Input

    DC Voltage

    One channel:DC -48V

    DC Current

    12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access

    State Grid Monitoring

    One channel:DC 0-5V

    Overload

    Voltage: 1.2 times for 1 second, 2 times for 1 second; Current: 1.2 times for 1 second, 10 times for 1 second

    Frequency

     

    Resolution

    The voltage output accuracy is 0.01V, the current output accuracy is 0.01A, the power output accuracy is 0.01kW, and the power output accuracy is 0.01kWh

    Function

    Basic Function

    Monitoring equipment system time, total voltage, total output current, total power, total electrical energy, voltage of each sub channel, current of each sub channel, power of each sub channel, electrical energy of each sub channel; RS485 communication

    Alarm Function

    DC voltage output too low alarm, DC voltage output too high alarm, one-time power-off alarm, module voltage loss alarm, metering sub channel error alarm, internal program error alarm, clock error alarm, memory unit failure alarm, AC input power failure alarm

    Timing function

    Support broadcast timing, remote timing calibration of metering module can be carried out through RS485 communication interface

    Communication

     

    Hall power supply

    A set of ±12V power output

    Humidity And Temperature

    4 Channels NTC Temperature Monitoring:Temperature:-20-100℃(Accuracy±2℃)

    Humidity:20-90%RH(Accuracy ±5%RH)

    Auxiliary power

    Voltage Range

    DC -40V~-60V

    Power consumption

    The whole device≤2W (without Hall power supply output)

    Storage

    It has the storage function of historical energy data and historical alarm information

    Insulation resistance

    ≥40MΩ

    Environment

    Temperature

    Working Temperature:-20℃~+60℃;Storage Temperature:-40℃~+70℃

    Humidity

    ≤98% no condensation, no corrosive gas place

    Altitude

    ≤4000m

    DIMENSION

    dimension

    Recommend Hall Current Sensor

    Model

    Specification

     1

    AHKC-EKA

    50A/5V Diameter Φ40mm

     2

    AHKC-EKB

    100A/5V Diameter Φ40mm

     3

    AHKC-K

    200A/5V  Diameter Φ64*16mm

    Wiring Terminals and Connections

    AMC200L-12DE


    Wiring Terminal Instruction-1

    Wiring Terminal Instruction-2

    Terminal Number

    Definition

    Instruction

    Remark

    1

    V+

    Auxiliary power

    DC 40-60V

    2

    V-

    11

    U+

    Voltage input

    DC 48V

    14

    U-

    21

    A

    Communication

    RS485 Communication

    22

    B

    30

    DI1

    Switch input

    Passive dry contact input

    31

    DI2

    32

    DI3

    33

    DI4

    39

    COM2

    34

    DI5+

    Active switch input

    AC 220V state grid or generator signal access

    35

    DI5-

    36

    DI6+

    37

    DI6-

    40

    D01

    relay output

    AC 250V/3A  DC 30V/3A;

    Normally open contact output; contact capacity:

    AC 250V/3A  DC 30V/3A;

    42

    DO2

    49

    COM1

    51

    +12V

    Hall Current sensor power supply

    Provide power to 12 hall current sensor at the same time

    52

    12G

    53

    -12V

    61

    AI+

    State Grid Monitoring

    DC 0-5V

    62

    AI-

    91

    T1

    NTC Temperature Monitoring

    Temperature Range:-20-100℃(Accuracy ±2℃)

    92

    T2

    93

    T3

    95

    T4

    94

    COM3

    97

    VSS

    Humidity And Temperature Monitoring

     

    98

    Data

    99

    Clk

    100

    VDD

     

    CH1-CH4

    Number of current Circuit

    One CHx represents 3 single-phase DC circuits, AMC200L-12DE can connect up to 12 single-phase circuits;

    Voltage, current and Hall current sensor wiring method (the figure below takes one channel as an example)


    Wiring Terminal Instruction-3

    AMC200L Voltage Current And Hall Current Sensor Wiring Method

    Note: A group of two Hall connecting lines needs to be connected to the M terminals. For example: the yellow lead wire of one connecting line is a group of yellow and black, corresponding to the yellow part of the above picture, and needs to be connected to the same group of yellow lines and black lines.

    Humidity And Temperature Sensor Wiring Method

    Wiring Terminal Instruction-4

    INSTALLATION INSTRUCTION

    1

    Din Rail Installation

    Download_file
    [Certificate 2023.06.21] CE Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] CE-RED Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] IEC Certificate ADW300 Series
    Download_file
    [Certificate 2023.06.21] LVD Certificate of ADW300 Series
    Download_file
    [Datasheet 2023.06.21] ADW300 3-phase Wireless Energy Meter
    Download_file
    [Instruction 2023.08.31] ADW300 Common FAQ & Trouble Shooting
    Download_file
    [Instruction 2023.08.31] ADW300 Keypad Configuration Manual