ARTM-24 24 Channels Wired Temperature Measuring Device
OVERVIEW
ARTM-24 temperature monitoring device can be connected to NTC, PT100/PT1000, thermocouple sensors, mainly used in low-voltage electrical nodes, transformer windings, motor windings and other places to measure temperature.
MAIN PARAMETERS
|
Technical Features Function |
Features |
|
|
ARTM-24 |
||
|
Number of measurement channels |
24 |
|
|
Input signal |
NTC:R25=10.00kΩ;B25/50=3380K; NTC:R25=50.00kΩ;B25/50=4150K; NTC:R25=100.00kΩ;B25/50=3950K; PT100/PT1000:Three-wire system; Thermocouple supports K, T, J, E, N types. |
|
|
Measurement Range |
NTC:-40℃~140℃; PT100: Maximum support -200℃~850℃, the actual range depends on PT100; PT1000: Maximum support -200℃~850℃, the actual range depends on PT1000; Thermocouple: maximum support -200℃~1372℃, the actual range depends on the thermocouple model. |
|
|
Accuracy class (standard signal) |
NTC:±1℃; PT100/PT1000:-200℃~200℃,±1℃;+200℃~850℃,±1%; Thermocouple: 1%. |
|
|
Auxiliary power |
voltage range |
AC85~265V/DC100-350V,DC12~30V |
|
Power consumption |
<=2W |
|
|
Alarm Output |
Channel |
2 groups of normally open |
|
Capacity |
AC250V/5A,DC30V/5A |
|
|
Temperature and humidity input |
Channel |
1 (optional) |
|
Temp |
±1℃ |
|
|
HUM |
±3% |
|
|
Communication |
Protocol |
MODBUS-RTU |
|
Interface |
RS485 |
|
|
Baud rate |
2400,4800,9600,19200 |
|
|
Environment |
TEMP |
-20℃~55℃ |
|
HUM |
<=95% |
|
DIMENSION
APPLICATION SCENARIOS
WIRING DIAGRAM
PT100 Wiring Method
No. 11~13 are the first terminal of PT100/PT1000, No. 13~15 are the second terminal of PT100/PT1000, and so on. PT100/PT1000 has one A line and two B lines. Connect the A line of the PT100/PT1000 to the terminal number labeled A, and connect the two B lines to the terminal numbers labeled B and C.
NTC Wiring
No. 12~13 are the terminals of the NTC‘s channel 1, No. 13~14 are the terminals of the NTC’s channel 2, and so on.
Thermocouple Wiring
11~12 is the 1st thermocouple terminal, 11 is connected to V-, 12 is connected to V+, 14~15 is the 2nd thermocouple terminal, 14 is connected to V+, 15 is connected to V-, and so on.
INSTALLATION INSTRUCTION


ARTM-8L rail (DIN35mm) installation