Leave Your Message
ARTM-24 24 Channels Wired Temperature Measuring Device
Wireless&Wired Temperature Monitoring Device
Products Categories
Featured Products

ARTM-24 24 Channels Wired Temperature Measuring Device

● 24 channels PT100/PT1000/NTC/Thermocouple monitoring

● Accuracy:NTC:±1℃;PT100/PT1000:-200℃~200℃,±1℃;+200℃~850℃,±1%; Thermocouple: 1%.

● AC85~265V/DC100-350V,DC12~30V power supply

● 2 channels alarm

● Modbus RTU protocol,RS485 interface

    OVERVIEW

    ARTM-24 temperature monitoring device can be connected to NTC, PT100/PT1000, thermocouple sensors, mainly used in low-voltage electrical nodes, transformer windings, motor windings and other places to measure temperature.

    MAIN PARAMETERS

                  

                     Technical Features   

    Function         

    Features

    ARTM-24

    Number of measurement channels

    24

    Input signal

    NTC:R25=10.00kΩ;B25/50=3380K;

    NTC:R25=50.00kΩ;B25/50=4150K;

    NTC:R25=100.00kΩ;B25/50=3950K;

    PT100/PT1000:Three-wire system;

    Thermocouple supports K, T, J, E, N types.

    Measurement Range

    NTC:-40℃~140℃;

    PT100: Maximum support -200℃~850℃, the actual range depends on PT100;

    PT1000: Maximum support -200℃~850℃, the actual range depends on PT1000;

    Thermocouple: maximum support -200℃~1372℃, the actual range depends on the thermocouple model.

    Accuracy class (standard signal)

    NTC:±1℃;

    PT100/PT1000:-200℃~200℃,±1℃;+200℃~850℃,±1%;

    Thermocouple: 1%.

    Auxiliary power

    voltage range

    AC85~265V/DC100-350V,DC12~30V

    Power consumption

    <=2W

    Alarm Output

    Channel

    2 groups of normally open

    Capacity

    AC250V/5A,DC30V/5A

    Temperature and humidity input

    Channel

    1 (optional)

    Temp

    ±1℃

    HUM

    ±3%

    Communication

    Protocol

    MODBUS-RTU

    Interface

    RS485

    Baud rate

    2400,4800,9600,19200

    Environment

    TEMP

    -20℃~55℃

    HUM

    <=95%

    DIMENSION

    dimensionem9

    APPLICATION SCENARIOS

    WIRING DIAGRAM

    No. 1 and 2 are auxiliary power terminals, No. 3 and 4 are DO1 output, No. 5 and 6 are DO2 output, No. 7 and 8 are terminals B and A of RS485 interface, No. 71~74 are V+, CLK, DATA, V- terminals for temperature and humidity

    PT100 Wiring Method

    No. 11~13 are the first terminal of PT100/PT1000, No. 13~15 are the second terminal of PT100/PT1000, and so on. PT100/PT1000 has one A line and two B lines. Connect the A line of the PT100/PT1000 to the terminal number labeled A, and connect the two B lines to the terminal numbers labeled B and C.

    PT100 WIRING92n

    NTC Wiring

    No. 12~13 are the terminals of the NTC‘s channel 1, No. 13~14 are the terminals of the NTC’s channel 2, and so on.

    NTC WIRING0g7

    Thermocouple Wiring

    11~12 is the 1st thermocouple terminal, 11 is connected to V-, 12 is connected to V+, 14~15 is the 2nd thermocouple terminal, 14 is connected to V+, 15 is connected to V-, and so on.

    Thermocouple WIRINGf3w

    INSTALLATION INSTRUCTION

    ARTM-24 temperature monitoring device use guide rail (DIN35mm) installation method.
    INSTALLATIONd2binstallation-2374

    ARTM-8L rail (DIN35mm) installation

    Download_file
    [Certificate 2023.06.21] CE Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] CE-RED Certificate of ADW300 Series
    Download_file
    [Certificate 2023.06.21] IEC Certificate ADW300 Series
    Download_file
    [Certificate 2023.06.21] LVD Certificate of ADW300 Series
    Download_file
    [Datasheet 2023.06.21] ADW300 3-phase Wireless Energy Meter
    Download_file
    [Instruction 2023.08.31] ADW300 Common FAQ & Trouble Shooting
    Download_file
    [Instruction 2023.08.31] ADW300 Keypad Configuration Manual