ASCB1-63-Cxx 1P Single Phase Smart Miniature Circuit Breaker
OVERVIEW
ASCB1 series intelligent smart circuit breakers are applied to low-voltage terminal distribution networks inindustrial,commercial,civil buildings and infrastructure fields in residential buildings andsimilar places.The intelligent micro circuit breaker is used with the intelligent gateway toconduct real-time monitoring of the key electrical parameters of the power line,such asvoltage,current,power,temperature,leakage,energy consumption,etc.,and has remotecontrol,abnormal warning,accident trip warning alarm,electric energy metering statistics,fault positioning and other functions.This series of products can be selected from unipole,2 pole,3 pole,4 pole.
MAIN PARAMETERS
|
Model |
ASCB1-63 |
ASCB1LE-63 |
|
|
Pole |
1P/2P/3P/4P |
2P/4P |
|
|
Grade of Shell |
63A |
||
|
Rated Voltage |
230V(1P/2P)、400V(3P/4P) |
||
|
Rated Current |
6A,10A,16A,20A,25A,32A,40A,50A,63A |
||
|
Instantaneous Unbuckle Type |
C/D |
||
|
Rated Short-circuit |
6000A |
||
|
Protec |
0ver- |
|
|
|
Short- |
|
||
|
|
|
||
|
0ver- |
Default 110%rated voltage alert,120%rated voltage trip with |
||
|
Under- |
Default 90%rated voltage alert,80%rated voltage trip with |
||
|
Over- |
Default 80℃ alert,100℃ trip,the threshold is ad justable |
||
|
Leakage |
No |
Default 20mA alert,30mA trip, |
|
|
Leakage self- |
No |
Manual button self-inspection |
|
|
Mechanical Life |
20000 times |
||
|
Electrical Life |
6000 times |
||
|
Levels of |
IP20 |
||
|
Connection |
1-35mm² |
||
|
Elevation Requirements |
2000m
|
||
|
Ambient Temperature
|
-10℃~55℃,the average temperature at 24h was no higher than 40℃
|
||
|
Environmental Requirements |
No explosion hazard, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibration |
||
|
Relative Humidity |
At +40℃,the relative humidity of the air is 50%and can have high relative humidity at lower temperatures |
||
|
Storage Temperature |
-20℃-70℃ |
||
|
Class of Pollution |
II |
||
|
Installation Type |
IⅢ |
||
|
Installation Method |
Standard 35mm guide rail installation |
||
BENEFITS AND ADVANTAGE
System
Measurement and control
DIMENSION
APPLICATION SCENARIOS
PHOTOS ON SITE



WIRING DIAGRAM
Front View
Top View

INSTALLATION INSTRUCTION

Step1: Use the communication cable provided with the gateway to connect the RS-485 port on the gateway to the BUS port of the circuit breaker.

Step2: Insert the barbed side of the connecting wire of the circuit breaker into the external terminal of the previous circuit breaker toward the outside of the terminal, and the colors should be in one-to-one correspondence.

This is a paragraph