PZ96L-DE DC Multi-function Energy Meter
OVERVIEW
PZ Series DC energy meter is designed for DC panel, solar power supply, telecom base station, charging pile and other applications. This series of energy meter can measure the voltage, current, power, forward and reverse energy in DC system. It can not only be used for local display, but also be connected with industrial control equipment and computer to form a measurement and control system. At the same time, it has a variety of peripheral interface functions for users to choose: with RS-485 communication interface, using Modbus-RTU protocol; It can be equipped with relay alarm output and switch input / output. According to different requirements, through the instrument panel buttons, the transformation ratio and communication are set and controlled.
MAIN PARAMETERS
|
Technical parameter |
index |
|||
|
Signal |
DC voltage |
input range |
0~100V,0~500V,0~1000V,1500V(only PZ96(L)) |
|
|
Input impedance |
≥6kΩ/V |
|||
|
DC current |
input range |
0~9999A(External shunt or Hall element, programmable range) |
||
|
Diverter |
The support output are 50mV and 75mV |
|||
|
Hall sensor |
The support output are 0 ~ 20mA, 0 ~ 5V,4~20mA(unipolar) ,etc |
|||
|
Consumption |
≤1mW |
|||
|
Overload |
1.2 times continuous normal operation, 2 times continuous 1 second |
|||
|
Accuracy class |
0.5 class |
|||
|
Pulse constant |
Voltage and current specifications:750V、 300A ,default pulse constant:100imp/kWh |
|||
|
Voltage and current specifications:1000V、300A ,default pulse constant:100imp/kWh |
||||
|
Voltage and current specifications:1000V、200A ,default pulse constant:100imp/kWh |
||||
|
Functions |
Measurement |
measure DC voltage U, current I and power P,When the current input is hall sensor(4~20mA output),the current only support unipolar metering. |
||
|
Metering |
measure current combined energy, forward energy and reverse energy,When the current input is hall sensor(4~20mA output),the electric energy only support unipolar metering. |
|||
|
Time sharing function |
Each year can be divided into 4 time zones. Each time zone table can be set with 12 daily time periods and 4 rates (F1, F2, F3, F4 are SHARP,PEAK,SHOULDER and OFF-PEAK). The minimum interval of time periods is 15 minutes. Time periods can be set across zero(LCD Meter only) |
|||
|
Historical data statistics function |
Count historical energy of last 12 months (energy of each rate)(LCD Meter only) |
|||
|
Switch input/ output function |
PZ72 has two switch output and two switch input. PZ96 has two switch output and four switch input. The switch output is relay output, which can realize remote control and alarm output. The switch input can not only collect and display the local switch status information, but also realize the remote transmission function through the RS485 of the instrument, namely the remote signaling function. |
|||
|
Display |
LCD(backlight delay time adjustable)or LED |
|||
|
Communication |
RS485 interface; half duplex, photoelectric isolation; Modbus-RTU protocol; baud rate 1200, 2400, 4800, 9600, 19200, 38400bps optional, modulation infrared fixed 1200bps. |
|||
|
Switch input/ output |
DI |
Dry contact input, built-in power supply, photoelectric isolation |
||
|
DO |
Two relay output, normally open contact, capacity 2A /30VDC or 2A/250VAC |
|||
|
operating voltage |
Voltage range |
85~265VAC、50/60Hz; 20~60VDC; 12VDC; 100~350VDC(declare in order) |
||
|
consumption |
≤2W |
|||
|
Insulation resistance |
≥100MΩ |
|||
|
Withstand voltage |
3KV / 1min between power supply terminal group and signal input / output terminal group(RMS) |
|||
|
Environment |
temperature |
Operating temperature:-40℃~+60℃;Storage temperature:-40℃~+70℃ |
||
|
humidity |
≤ 93%RH,no condensation,no corrosive gas |
|||
|
altitude |
≤ 2500m |
|||
DIMENSION
PACKAGE
|
Packaging Overview (Minimum) |
|
|
|
Packing Dimension and Weight (Minimum) |
Minimum Package Contain 1 pcs Products Dimension: 230mm*145mm*120mm
|
Total N.W. (1 pcs) 0.71 KG |
|
Packing Dimension and Weight (Large) |
Large Package Contain 48 pcs Products Dimension: 615mm*480mm*395mm
|
Total N.W. (36 pcs) 16.09 KG |
|
Average Lead Time |
Manufacturing: 3~4 days (If paired with system need extra 1~2 days for adjustment)
|
Shippment: 8~9 days (World Wide Shipment) |
|
Product HS Code |
9028309000
|
|
|
CO Country of Origin |
China |
|
WIRING DIAGRAM
DC Voltage Signal (1000V DC) Input via direct Connection & DC Current Signal (75mV DC) input via -/75mV Shunts
DC Voltage Signal (1000V DC) Input via direct Connection & DC Current Signal (0~20mA or 4~20mA DC) input via Hall Sensors
INSTALLATION INSTRUCTION